Add to Cart
Description:
Sewage Combination air release valve provide 3 functions:
1. Large air release
1-1. During water filling the pipeline, float will stay at its original position. (open)
1-2. Let large air out of valve thru big nozzle.
2. Small air release
2-1.When the water level comes up to the top, float will be up to its close position and close the sealing arc- big orifice and small orifice.
2-2.The air (2% of solved air in water ) are continuously coming out from water and gather at the top of the valve.
2-3.The float will be driven down and let small pocket out thru small orifice.
2-4.The sealing arc will still be in close position until empty of water
3. Large air intake during draining of the pipeline.
3-1.Float will drop down when empty of pipeline.
3-2.Large air will come into the pipeline thru valve.
3-3.Preventing from collapse of pipeline and break vacuum.
3-4.Protect the sealing o-ring from clogging in the pipeline.
Features:
. Advanced design: Simple mechanism and strong float to prevent cracking during sudden water hammer& quick closure.
. Drain boss at the top & bottom for cleaning.
. No arms or levers to prevent vibrating, bending, direct closure of the fl oat.
. Fully fusion epoxy coated inside and outside of valve body for long term services.
. Manufacturing standard : BS EN1074-4, AWWA C512
. Flange drilling and dimension : BS EN 1092 and BS EN 558 and ANSI flange.
Service Fields:
For sewage water system.
Technical Data:
Size range: DN 50-200MM
Pressure ratings:1.0Mpa,1.6Mp (Flange)
Working temperature: -10°-80°C.
Flow media: sewage water.
Please consult factory for PN25 and antishock device whenever there is waterhammer issue.
Quick Selection Table | |||||
Water Flow Rate CMH | 1360 | 4160 | 8500 | 19100 | 33400 |
Main pipe size MM | 80-400 | 400-700 | 750-1000 | 1050-1500 | 1500-2000 |
Size of SKAR MM | 50 | 80 | 100 | 150 | 200 |
Material:
Dimension: